Finally! Fault-tolerant I/O to make your job easier!
Real-time Ethernet Ring
Redundant Power Survivability
Self-Resetting Fuses
Independent Watchdog/Health Monitoring
"Undo" Web Features and much more...
|
|
|
|
|
|
Product
Highlights:
A Remarkable Breakthrough for Industrial Automation |
- 32 I/O
in each innovative quick install, compact module
- Dual Ethernet
ports with Real-time
Ring™ redundancy
- Spectacular
web
interface - complete and easy to use
- Process
Quality I/O - hot
swap, watchdog, validation ...
- Lightning
fast 1 mS I/O updates, infinitely expandable
- Innovative Etherbus® PoE option - eliminate power wiring
- Truly
open I/O - 20 years of design life - the ultimate I/O
- Packed
with innovative features - please read on....
|
| |
EtherTRAK-2
is our truly rugged breakthrough product packed with innovations
that are revolutionizing process control systems. Explore the
next
generation
of "Process Quality I/O". They offer the ultimate price/performance
for the process control industry with self-contained I/O modules
that integrate with any control system.
SIXNET knows industrial –
Our 30-year track record as the #1 supplier of industrial
equipment for extreme environments says it all. As a Total
Quality supplier of reliable, ever improving products built
for the most rugged applications on the planet, our newest
generation of I/O will exceed expectations. |
| |
| Get
More Information on EtherTRAK-2: |
|
|
|
| |
| Features:
|
|
| |
| High
Performance, Flexible I/O |
- 32
I/O channels in a space-saving package
- Flexible
mix of functions in a single module
- 16
bit analog for extreme accuracy
- 1
mS I/O polling for lightning fast performance
- Advanced
counter functions with 32 bit reporting
- Watchdog monitoring and reporting
- Small,
modular footprint - just 9
cm on a DIN rail
|
| Flexible,
Redundant, "Multiport" Communications |
- Dual
Ethernet ports eliminate a need for switches
- Real-time
Ring™ Switch for fault-tolerant redundancy
- Power
over Ethernet reduces cabling & costs
- RS485,
USB & optional RS232 ports for flexibility
- Supports
industry standard Modbus messaging
- Embedded
I/O concentrator polls additional I/O
|
| Extraordinary
Features Make Your Job Easier
|
- Web-based I/O configuration and monitoring
- Stores
project documentation in a quick-access web server
- Hot
swap for instant installation and maintenance
- OEM
customizable components and labeling
- Vibration
tolerant, space saving package
|
| True
Industrial Design |
- Industrial
-40 to +75°C operating range ... More
info
- UL /
CSA (CUL), FCC and CE rated ... More
info
- Hazardous
locations rated for Class I, Div. 2 (Zone 2) areas ... More
info
- Unique
20-year support and service policy ... More
info
|
| |
| General
I/O Module Characteristics (all Models) |
Power
supply voltage
|
10-30
VDC |
Input
current requirement
|
100
mA @ 24 VDC typical |
| Etherbus®
PoE (EB- only) |
10
Watts at 60°C for user loads
Derate to 5 Watts at 75°C |
| I/O
registers available for additional expansion I/O |
512
discrete inputs and outputs plus
256 analog inputs and output registers |
| Unique
station addresses |
16,000+
(SIXNET) or 247 (Modbus) |
 |
 |
|
| |
| Ethernet |
| Ethernet
ports |
10/100BaseTx
(auto-detecting) |
| Connection |
RJ45 (auto-crossover) |
| Isolation |
1500 Volts
RMS 1 minute (60 Hz.) |
| Message
response time |
Less than
1 mS per message |
| Diagnostic
LED on each port |
On solid indicates
link and blinking indicates activity |
| Protocols
supported |
TCP/IP, ARP,
UDP, ICMP, DHCP, Modbus/TCP, SIXNET and more |
| Real-time Ring™ |
5mS per hop
recovery time |
| Independent networks |
1 or 2 networks,
each with unique MAC and IP address |
 |
 |
| RS485
port |
Screw terminals (485+, 485-, GND) (2-wire half-duplex) |
| RS485
networking |
Up to 32 (full-load) stations |
| RS485
distance |
Up to 0.5 miles (baud rate dependant) |
| Baud
Rates |
From 300
to 57,600 baud |
| RS232
Port (optional) |
(TD, RD, CTS, RTS, GND) |
| 2nd
RS232 Port (special order) |
RJ45 (TD, RD, CTS, RTS, CD, DTR, DSR, GND) |
| Protocols:
master & slave |
SIXNET & Modbus RTU/ASCII |
| Diagnostic
LEDs |
Transmit (TD) & Receive (RD) |
| Flow Control |
Hardware,
software or RTS-partyline (for radios and RS485) |
 |
 |
| Environmental
& Standards |
|
| Operating
Temperature |
-40 to 75°C |
| Storage
Temperature |
-40 to 85°C |
| Humidity |
5 to 95% RH
(non-condensing) (optional conformal coating) |
| Vibration |
IEC68-2-6 |
| Flammability |
UL 94V-0 materials |
| Electrical Safety |
UL 508, CSA C22.2/14; EN61010-1 (IEC1010); CE |
| EMI emissions |
FCC part 15, ICES-003, Class A; EN55022; EN61326-1; CE |
| EMC immunity |
EN61326-1 (EN61000-4-2,3,4,6); CE |
| Surge withstand |
IEEE-472 (ANSI C37.90) |
| Hazardous locations (Class 1, Div 2, Groups
A, B, C, D) |
UL 1604, CSA C22.2/213, Cenelec EN50021 Zone 2 |
| Marine & Offshore |
Tested and/or
verified to meet various marine and maritime standards such as
DNV No. 2.4, Lloyds and ABS |
| ISO9001:2000 |
Certified "Total
Quality" company ... More
info |
 |
 |
| Case |
Slim line,
ideal for DIN rail mounting |
| Material |
Impact resistant
Lexan polycarbonate |
| Protection |
IP30 protection
from dust and debris |
| Mounting |
DIN rail or
direct to panel (no optional kits or accessories required) |
| Dimensions |
5.5" x
3.5" x 5.1" (14 x 8.9 x 13 cm) ... See
diagram |
| Weight |
13.6 oz. (0.39
kg) |
 |
 |
| |
| Ordering
Guide: |
|
| |
EtherTRAK-2
with Wiring Base |
Including
the PoE "Etherbus®" Option |
DI
|
DO
|
AI
|
AO
|
Description
|
| E2-MIX24880-D |
EB-MIX24880-D |
24
|
8
|
8
|
0
|
Combination
I/O with 1 isolated input counter * |
| E2-MIX24882-D |
EB-MIX24882-D |
24
|
8
|
8
|
2
|
Combination
I/O with 2 analog outputs ** |
| E2-32DI24-D |
EB-32DI24-D |
32
|
|
|
|
32
inputs (10-30 VDC) |
| E2-16DI24-D |
EB-16DI24-D |
16
|
|
|
|
16
individually isolated channels, 10-30 VDC/VAC with
counters |
| E2-16DIAC-D |
- |
16
|
|
|
|
16
individually isolated inputs, 120 VAC nominal |
| E2-32DO24-D |
EB-32DO24-D |
|
32
|
|
|
High
density discrete outputs |
| E2-16DO24-D |
EB-16DO24-D |
|
16
|
|
|
Individually
isolated 1 Amp outputs with self-resetting fuses |
| E2-32AI20M-D |
EB-32AI20M-D |
|
|
32
|
|
High
density 16 bit 4-20mA inputs with self-resetting fuses |
| E2-32AI10V-D |
EB-32AI10V-D |
|
|
32 |
|
Voltage
inputs |
| E2-16AI20M-D |
EB-16AI20M-D |
|
|
16
|
|
16
channels 4-20mA inputs with self-resetting fuses |
| E2-8AO20M-D |
EB-8AO20M-D |
|
|
|
8
|
4-20mA
analog outputs |
| E2-16AI-8AO-D |
EB-16AI-8AO-D |
|
|
16 |
8 |
16
4-20mA inputs plus 8 4-20mA outputs |
| E2-16INS-D |
EB-16INS-D |
|
|
16TC
|
|
Instrumentation
thermocouples |
| E2-8INS-D |
EB-8INS-D |
|
|
8TC
|
|
Instrumentation
thermocouples |
| E2-8RTD-8DI-D |
EB-8RTD-8DI-D |
8
|
8
|
8RTD
|
|
RTD
(100 Ohm platinum), -200 to 850°C plus 8 auxiliary
discrete in/out channels |
|
Note:
* 24 maximum DI’s are listed, 8 of which can be configured as either
DI or DO. The discrete outputs are protected by self-resetting fuses.
** EB part number prefix (above) is for modules that include the optional
Etherbus® PoE feature. Standard product part numbers begin with E2. |
| |
| Related
Products: |
|
| Download
AutoCAD Drawings:
AutoCAD
2004 LT ".dwg" file or AutoCAD
R12/LT2 ".dxf" file
|
|
|
Certified
to Perform
 |