ET-GT-232-1 Performance Specifications

Ethernet port

10BaseT at 10Mbps

Ethernet Protocols supported

SIXNET "I/O for Windows", Modbus ASCII, Modbus RTU, many user protocols *

Connection types supported

UDP/IP (many connections), TCP/IP (2 sessions max.)

Passthru expansion per node (UDP/IP)

Up to 32 RemoteTRAK, EtherTRAK, Modbus compatible devices or other devices when using an RS485 or RS232 passthru connection

Passthru expansion per node (TCP/IP)

One additional SIXNET or Modbus compatible device or other device when using an RS485 or RS232 passthru connection

 

 

Serial protocols

SIXNET, Modbus ASCII or Modbus RTU, many user protocols *

RS232 port

TD, RD, RTS, CTS, DTR, GND

Max. serial port baud rate

115,200

Ethernet isolation

1200 VRMS 1 minute

Required supply voltage

10-30 VDC (0.5 watt typical)

Operating temperature range

-30 to 70° C

Storage temperature range

-40 to 85° C

Humidity (non-condensing)

5 to 95 %

Electrical safety

UL 508, CSA22.2/14; EN6101-1 (IEC1010), CE

EMI emissions

FCC part 15, ICES-003, Class A; EN55022, CE

EMC immunity

EN50082-1 (IEC801-2,3,4) CE

Hazardous locations

UL 1604, CSA C22.2/213-M1987, (Class I, Div. 2, Groups A, B, C, D), EN50021 (zone 2)

Marine/offshore locations

Det Norske Veritas (DNV) No. 2.4 (Class A and B)

 

 

* Many user protocols are supported. Refer to the Usage Tips for more information.

 

 