Industrial Ethernet |
|
q |
|
|
|
|
|
ET-GT-485-1 Performance Specifications
|
Ethernet port |
10BaseT at 10Mbps |
|
Ethernet Protocols supported |
SIXNET "I/O for Windows", Modbus ASCII, Modbus RTU, many user protocols * |
|
Connection types supported |
UDP/IP (many connections), TCP/IP (2 sessions max.) |
|
Passthru expansion per node (UDP/IP) |
Up to 32 RemoteTRAK, EtherTRAK, Modbus compatible devices or other devices when using an RS485 or RS232 passthru connection |
|
Passthru expansion per node (TCP/IP) |
One additional SIXNET or Modbus compatible device or other device when using an RS485 or RS232 passthru connection |
|
|
|
|
Serial protocols |
SIXNET, Modbus ASCII or Modbus RTU, many user protocols * |
|
RS485 port |
2 wire (TD, RD, GND) |
|
Max. serial port baud rate |
57,600 |
|
Max. # of RS485 devices |
32 |
|
Max. RS485 cable distance |
1 km w/ 24 AWG wire & 57,600 baud |
|
|
2 km w/ 20 AWG wire & 38,400 baud |
|
|
3.5 km w/ 18 AWG wire & 19,200 baud |
|
RS485 isolation |
1200 VRMS 1 minute |
|
Ethernet isolation |
1200 VRMS 1 minute |
|
Required supply voltage |
10-30 VDC (0.5 watt typical) |
|
Operating temperature range |
-30 to 70° C |
|
Storage temperature range |
-40 to 85° C |
|
Humidity (non-condensing) |
5 to 95 % |
|
Electrical safety |
UL 508, CSA22.2/14; EN6101-1 (IEC1010), CE |
|
EMI emissions |
FCC part 15, ICES-003, Class A; EN55022, CE |
|
EMC immunity |
EN50082-1 (IEC801-2,3,4) CE |
|
Hazardous locations |
UL 1604, CSA C22.2/213-M1987, (Class I, Div. 2, Groups A, B, C, D), EN50021 (zone 2) |
|
Marine/offshore locations |
Det Norske Veritas (DNV) No. 2.4 (Class A and B) |
* Many user protocols are supported. Refer to the Usage Tips for more information.