Industrial Ethernet |
|
q |
|
|
|
|
|
ET-16DO2 Performance Specifications
|
Number of output channels |
16 |
|
Output range |
10 – 30 VDC |
|
Max. output current per channel |
1 Amp |
|
Max. output current |
8 Amps (entire module) |
|
Max. OFF state leakage current |
0.05 mA |
|
Min. load current per channel |
0.1 mA |
|
Inrush current (100 mS surge) |
5 Amps |
|
Typical ON resistance |
0.3 Ohms |
|
Typical ON voltage (@ 1 Amp) |
0.3 VDC |
|
Time proportioned outputs |
Configurable for each channel (See note 2) |
|
Fastest scan rate (16 channels) |
2 mS (See note 1) |
|
Ethernet communications |
|
|
Isolation (from Ethernet port) |
1200 Volts RMS 1 Minute |
|
Required supply voltage |
10-30 VDC (0.75 watt typical) |
|
Operating temperature range |
-30 to 70° C |
|
Storage temperature range |
-40 to 85° C |
|
Humidity (non-condensing) |
5 to 95% |
|
Flammability (module plastic) |
UL 94V-0 materials |
|
Electrical safety |
UL 508, CSA C22.2/14; EN61010-1 (IEC1010), CE |
|
EMI emissions |
FCC part 15, ICES-003, Class A; EN55022, CE |
|
EMC immunity |
EN50082-1 (IEC801-2, 3, 4) CE |
|
Surge withstand |
IEEE-472 (ANSI C37.90) |
|
Vibration |
IEC68-2-6 |
|
Hazardous locations |
UL 1604, CSA C22.2/213-M1987, (Class I, Div 2, Groups A, B, C, D), EN50021 (zone 2) |
|
Marine/offshore locations |
Det Norske Veritas (DNV) No. 2.4 (Class A and B) |
Notes:
I/O register update time does not include external communications.
Time Proportioned Outputs control the duty cycle of the output in proportion to an analog output register value. The cycle time and minimum pulse time are configurable.
Specifications are subject to change. Consult the factory for the latest information.