Industrial Ethernet |
|
q |
|
|
|
|
|
ET-4RTD-4DI2 Performance Specifications
|
Number of RTD inputs |
4 |
|
RTD type |
100 ohm platinum, alpha = .00385 or .00392 |
|
Compatible lead configurations |
2, 3, or 4 wire |
|
Input range |
-200 to 850° C |
|
A/D resolution |
16 bits |
|
Scaled Resolution |
0.1° C |
|
Full scale accuracy (@20C) |
0.5° C |
|
Span & offset temp. coefficient |
+/- 25 ppm/° C |
|
Excitation current |
|
|
(pulsed to reduce self heating) |
250 uA |
|
Max. lead wire resistance |
100 ohms per side, balanced |
|
Input protection |
+/- 25 VDC |
|
Fastest scan rate (4RTDs) |
700 ms |
|
Fastest scan rate (4DIs) |
20 ms |
|
Number of discrete inputs |
4 |
|
Nominal discrete input range |
12/24 VDC/VAC |
|
Discrete input characteristics |
|
|
|
|
|
Ethernet communications |
|
|
Isolation (from Ethernet port) |
1200 Volts RMS 1 Minute |
|
Required supply voltage |
10-30 VDC (0.75 watt typical) |
|
Operating temperature range |
-30 to 70° C |
|
Storage temperature range |
-40 to 85° C |
|
Humidity (non-condensing) |
5 to 95% |
|
Flammability (module plastic) |
UL 94V-0 materials |
|
Electrical safety |
UL 508, CSA C22.2/14; EN61010-1 (IEC1010), CE |
|
EMI emissions |
FCC part 15, ICES-003, Class A; EN55022, CE |
|
EMC immunity |
EN50082-1 (IEC801-2, 3, 4) CE |
|
Surge withstand |
IEEE-472 (ANSI C37.90) |
|
Vibration |
IEC68-2-6 |
|
Hazardous locations |
UL 1604, CSA C22.2/213-M1987, (Class I, Div 2, Groups A, B, C, D), EN50021 (zone 2) |
|
Marine/offshore locations |
Det Norske Veritas (DNV) No. 2.4 (Class A and B) |
Specifications are subject to change. Consult the factory for the latest information.