ET-8INS Performance Specifications

Number of channels

8

Lowest voltage range

+/- 0.062 Volts

Maximum voltage range

+/- 10 Volts

Auto-polarity current range

4-20 mA and 0-20 mA

Thermocouple types (see note 1)

J,K,E,R,T,B,C,N,S

A/D resolution

16 bits (0.003%)

Full scale accuracy (@20° C)

+/- 0.02%

Input span & offset adjustability

+/- 25%

Span & offset temp. coefficient

+/- 30 ppm per ° C typical

Voltage range input impedance

200K Ohms

Current range input impedance

100 Ohms

CMRR (at 50/60 Hz)

140 dB

DMRR (at 50/60 Hz)

66 dB

Common mode input voltage

+/- 25 VDC between two input terminals

Common mode input voltage

1200 Volts between inputs and ground

No damage input voltage

+/- 50 VDC

Typical scan rate (all 8 channels)

800 mS - 1,000 mS, depending on

   using 100 mS / channel mode

signal types (revised 6/30/04)

   (See Notes 2 and 3 below)

 

Typical scan rate (all 8 channels)

300 mS - 500 mS, depending on

   using 60Hz-50 mS / channel mode

signal types (revised 6/30/04)

   (See Note 2 below)

 

Typical scan rate (all 8 channels)

400 mS - 600 mS, depending on

   using 50Hz-50 mS / channel mode

signal types (revised 6/30/04)

   (See Note 2 below)

 

Fastest scan rate (all 8 channels)

100 mS (revised 6/30/04)

   using 16 mS / channel mode

 

   (See Note 2 below)

 

 

 

Ethernet communications

See System Specs

Isolation (from Ethernet port)

1200 Volts RMS 1 Minute

Required supply voltage

10-30 VDC (1.6 watts typical)

Operating temperature range

-30 to 70° C

Storage temperature range

-40 to 85° C

Humidity (non-condensing)

5 to 95%

Flammability (module plastic)

UL 94V-0 materials

Electrical safety

UL 508, CSA C22.2/14; EN61010-1 (IEC1010), CE

EMI emissions

FCC part 15, ICES-003, Class A; EN55022, CE

EMC immunity

EN50082-1 (IEC801-2, 3, 4) CE

Surge withstand

IEEE-472 (ANSI C37.90)

Vibration

IEC68-2-6

Hazardous locations

UL 1604, CSA C22.2/213-M1987, (Class I, Div 2, Groups A, B, C, D), EN50021 (zone 2)

Marine/offshore locations

Det Norske Veritas (DNV) No. 2.4 (Class A and B)

 

Notes:

  1. Thermocouple inputs are cold-junction compensated and reported as °F or °C.

  2. These specifications apply to ET-8INS modules manufactured afterJuly 30, 2004. Performance characteristics of earlier modules may be different. Consult the factory for more information.

  3. The default analog input integration time for this module is 100 mS per channel. This mode is recommended for all applications where moderate noise filtering is desirable.

 

 

Specifications are subject to change. Consult the factory for the latest information.