Industrial Ethernet |
|
q |
|
|
|
|
|
ET-8INS Performance Specifications
|
Number of channels |
8 |
|
Lowest voltage range |
+/- 0.062 Volts |
|
Maximum voltage range |
+/- 10 Volts |
|
Auto-polarity current range |
4-20 mA and 0-20 mA |
|
Thermocouple types (see note 1) |
J,K,E,R,T,B,C,N,S |
|
A/D resolution |
16 bits (0.003%) |
|
Full scale accuracy (@20° C) |
+/- 0.02% |
|
Input span & offset adjustability |
+/- 25% |
|
Span & offset temp. coefficient |
+/- 30 ppm per ° C typical |
|
Voltage range input impedance |
200K Ohms |
|
Current range input impedance |
100 Ohms |
|
CMRR (at 50/60 Hz) |
140 dB |
|
DMRR (at 50/60 Hz) |
66 dB |
|
Common mode input voltage |
+/- 25 VDC between two input terminals |
|
Common mode input voltage |
1200 Volts between inputs and ground |
|
No damage input voltage |
+/- 50 VDC |
|
Typical scan rate (all 8 channels) |
800 mS - 1,000 mS, depending on |
|
using 100 mS / channel mode |
signal types (revised 6/30/04) |
|
(See Notes 2 and 3 below) |
|
|
Typical scan rate (all 8 channels) |
300 mS - 500 mS, depending on |
|
using 60Hz-50 mS / channel mode |
signal types (revised 6/30/04) |
|
(See Note 2 below) |
|
|
Typical scan rate (all 8 channels) |
400 mS - 600 mS, depending on |
|
using 50Hz-50 mS / channel mode |
signal types (revised 6/30/04) |
|
(See Note 2 below) |
|
|
Fastest scan rate (all 8 channels) |
100 mS (revised 6/30/04) |
|
using 16 mS / channel mode |
|
|
(See Note 2 below) |
|
|
|
|
|
Ethernet communications |
|
|
Isolation (from Ethernet port) |
1200 Volts RMS 1 Minute |
|
Required supply voltage |
10-30 VDC (1.6 watts typical) |
|
Operating temperature range |
-30 to 70° C |
|
Storage temperature range |
-40 to 85° C |
|
Humidity (non-condensing) |
5 to 95% |
|
Flammability (module plastic) |
UL 94V-0 materials |
|
Electrical safety |
UL 508, CSA C22.2/14; EN61010-1 (IEC1010), CE |
|
EMI emissions |
FCC part 15, ICES-003, Class A; EN55022, CE |
|
EMC immunity |
EN50082-1 (IEC801-2, 3, 4) CE |
|
Surge withstand |
IEEE-472 (ANSI C37.90) |
|
Vibration |
IEC68-2-6 |
|
Hazardous locations |
UL 1604, CSA C22.2/213-M1987, (Class I, Div 2, Groups A, B, C, D), EN50021 (zone 2) |
|
Marine/offshore locations |
Det Norske Veritas (DNV) No. 2.4 (Class A and B) |
Notes:
Thermocouple inputs are cold-junction compensated and reported as °F or °C.
These specifications apply to ET-8INS modules manufactured afterJuly 30, 2004. Performance characteristics of earlier modules may be different. Consult the factory for more information.
The default analog input integration time for this module is 100 mS per channel. This mode is recommended for all applications where moderate noise filtering is desirable.
Specifications are subject to change. Consult the factory for the latest information.