Industrial Ethernet |
|
q |
|
|
|
|
|
ET-MIX24880-D Performance Specifications
|
Ethernet Port |
10BaseT at 10 Mbps |
|
Ethernet communications |
|
|
Protocols |
SIXNET, Modbus RTU / ASCII |
|
Isolation (from Ethernet port) |
1200 Volts RMS 1 Minute |
|
|
|
|
|
|
|
RS485 Port |
Up to 38,400 baud |
|
Operation |
Master (passthru) or slave |
|
Supported modes |
Expansion I/O (as a master), distributed I/O |
|
(see the Usage Tips for details) |
or backup communications path (as a slave) |
|
Protocols |
SIXNET, Modbus RTU / ASCII |
|
Maximum distance |
Up to 0.5 mile (0.8 km) |
|
|
|
|
|
|
|
24 Discrete inputs* |
10-30 VDC |
|
Channels 1 through 8 |
Sinking or sourcing (as a group) |
|
Channels 9 through 24 |
Sourcing only |
|
Guaranteed ON voltage |
9 VDC |
|
Guaranteed OFF voltage |
5.0 VDC |
|
Guaranteed OFF current |
1.5 mA DC |
|
Input resistance & current |
10K Ohms & 2.4 mA @ 24VDC |
|
Filtered ON/OFF delay |
25 mS (10 Hz max. counting) |
|
Fast ON/OFF delay |
4 mS (100 Hz max. counting) |
|
Counters on 1st 8 channels |
Up to 50 KHz on channels 1 and 2 |
|
Counter modes |
Count up, run time and pulse rate |
|
|
|
|
|
|
|
8 Discrete Outputs * |
10-30 VDC |
|
Max. output current |
1A per channel, 8A per module |
|
Max. OFF state leakage |
0.05 mA |
|
Min. load |
1 mA |
|
Inrush current |
5 Amps (100 mS surge) |
|
Typ. ON resistance / volt |
0.3 Ohms / 0.3 VDC (@1A) |
|
|
|
|
|
|
|
8 Analog Inputs |
4-20 mA (other ranges available) |
|
A/D resolution |
16 bits (0.003%) |
|
Full scale accuracy |
+/-0.1% (@20°C) |
|
Span & offset temp. coeff. |
+/-50 ppm per degree C |
|
Input impedance |
100 Ohm |
|
Current protection |
Self-resetting fuses |
|
DMRR |
66 dB at 50/60 Hz |
|
Short circuit protection |
Current limiting |
|
Fastest scan time (all 8 channels) |
200 mS (Rev. 1.02 and newer modules), |
|
|
1,000 mS (Rev. 1.01 and earlier) |
|
|
|
|
|
|
|
Environmental |
DIN rail or panel mount |
|
Required user supply |
10-30 VDC |
|
Power (typ.) @ 24 VDC |
1 Watt, 42 mA (excluding I/O) |
|
Operating temp. range |
-40 to +70°C |
|
Storage temp. range |
-40 to +85°C |
|
Humidity (non-conden.) |
5 to 95% RH |
|
Vibration |
IEC68-2-6 |
|
Electrical safety |
UL508, CSA C22.2/14; EN61010 |
|
EMI emissions |
FCC part 15, ICES-003; EN55022 |
|
EMC immunity |
EN50082-1, EN61326-1 |
|
Surge withstand |
IEEE-472 |
|
Hazardous locations |
UL1604, CSA C22.2/213, EN50021, EEx nA II T4 X |
|
(Class 1, Div 2 / Zone 2) |
|
|
Marine/offshore locations |
Det Norske Veritas (DNV) No. 2.4 (Class A & B) |
* Note: Discrete I/O channels 16-24 can be configured (individually) to be discrete inputs or discrete outputs.