Modular I/O |
|
q |
|
|
|
|
|
ST-GT-ETH-xxP Performance Specifications
|
Max modules with expanders |
128 |
|
Max modules w/o expanders |
20 |
|
Max I/O (any mix) per gateway |
1024 |
|
Max addressable gateways |
16,000 |
|
Fastest I/O scan time |
5 mS |
|
ISaGRAF scan time |
Set by user |
|
|
|
|
Main Ethernet Port (SIXNET protocol): |
|
|
Ethernet Message Format: |
TCP/IP (See note) |
|
Data rate |
10 Mbits/sec |
|
AUI (DB15) |
Yes |
|
10BaseT (RJ-45 twisted pair) |
Yes |
|
|
|
|
Plant Floor RS232 Port: |
|
|
SIXNET Universal Protocol |
Yes |
|
Modbus ASCII or RTU mode |
Yes |
|
Default baud rate |
9600 |
|
Maximum baud rate |
38400 |
|
|
|
|
Memory Features: |
|
|
Flash memory |
1 Megabyte |
|
Battery backed RAM |
256K bytes (-24P), 1MB (-44P), 2MB (-54P) |
|
Real-time clock for datalogging |
Yes |
|
Clock resolution |
10 mS |
|
Typical accuracy |
+/- 15 sec/month |
|
|
|
|
Incoming supply voltage |
18 - 30 VDC |
|
Power consumption |
3 watts (less modules) |
|
Operating temperature range |
-30 to 70 degrees C |
|
Storage temperature range |
-40 to 85 degrees C |
|
Humidity (non-condensing) |
5 to 95 % |
|
Flammability (module plastic) |
UL 94V-0 materials |
|
Electrical safety |
UL 508, CSA C22.2/14; EN61010-1 (IEC1010), CE |
|
EMI emissions |
FCC part 15, ICES-003, Class A; EN55022, CE |
|
EMC immunity |
EN50082-1 (IEC801-2, 3, 4) CE |
|
Surge withstand |
IEEE-472 (ANSI C37.90) |
|
Vibration |
IEC68-2-6 |
|
Hazardous locations |
UL 1604, CSA C22.2/213-M1987, (Class I, Div 2, Groups A, B, C, D), EN50021 (zone 2) |
|
Marine/offshore locations |
Det Norske Veritas (DNV) No. 2.4 (Class A and B) |
Note: SIXNET protocol is sent over TCP/IP. Consult the factory for other protocols.