Product Catalog |
|
q |
|
|
|
|
|
SixTRAK IPm Performance Specifications
|
General |
Industrial PowerPC (32 bit data bus) |
|
Operating system |
Embedded LINUX |
|
Dynamic memory (RAM) |
16+ Megabytes -32bit, 0 wait states |
|
Program memory (Flash) |
16 Megabytes or 136 MB (-6350 model only) |
|
Datalogging memory (RAM) |
512K or 2 MB (battery-backed) |
|
Battery type |
Rechargeable lithium |
|
Max. back-up time after full charge |
1 Year |
|
Typical battery life |
10 Years |
|
|
|
|
Real-time clock |
For datalogging and more |
|
Resolution |
10 mS |
|
Accuracy (typical) |
+/- 15 Seconds per month |
|
|
|
|
Maximum local I/O |
1,024 |
|
Maximum distributed I/O |
50,000+(application dependent) |
|
Datalogging support |
Yes -SIXNET Sixlog |
|
IEC 61131 programming |
Yes -SIXNET ISaGRAF |
|
High Level C programming |
Yes -LINUX open software |
|
|
|
|
Ethernet ports (all) |
10/100BaseTx auto-detecting |
|
Connection |
RJ45 (auto-crossover) |
|
Protocols |
TCP/IP, ARP, UDP, ICNP, DHCP, Modbus ASCII & RTU, SIXNET Universal and more… |
|
Independent networks |
2 wth unique MAC and IP addresses |
|
Network port 1 |
1 shielded RJ45 connector |
|
Network port 2 |
4 shielded RJ45 connectors (linked via integrated Ethernet switch) |
|
Isolation protection |
1000 Volts |
|
|
|
|
Serial ports |
Up to 115,200 baud |
|
RS232 Port A |
RJ45 (TD, RD, CTS, RTS, CD, DTR, DSR, GND) |
|
RS232 Port B |
RJ45 (TD, RD, CTS, RTS, CD, DTR, DSR, GND) |
|
RS485 Port C |
Screws (485+, 485-, GND) (2-wire half duplex) |
|
Max. RS485 cable distance |
0.8 km (0.5 mile) w/ 24 AWG wire & 57,600 baud |
|
Protocols |
SIXNET & Modbus RTU/ASCII (master or slave); many others available in LINUX |
|
Flow control |
Hardware, software, half and full duplex (supports delayed RTS keying for multi-drop radio links) |
|
|
|
|
Environmental |
DIN rail or flat panel mount |
|
Input power |
10-30 VDC |
|
Input current |
150 mA @24 VDC (typical) |
|
Operating temperature |
-40 to +70° C |
|
Storage temperature |
-40 to +85° C |
|
Humidity |
5%to 95%RH (non-condensing) |
|
Flammability |
UL 94V-0 materials |
|
Electrical Safety |
UL 508,CSA C22.2/14;EN61010-1 (IEC1010); CE |
|
EMI emissions |
FCC part 15,ICES-003, Class A; EN61326-1; CE |
|
EMC immunity |
EN61326-1 (EN61326-4-2, 3, 4, 6); CE |
|
Surge withstand |
IEEE-472 (ANSI C37.90) |
|
Vibration |
IEC68-2-6 |
|
Hazardous locations |
UL 1604,CSA C22.2/213, |
|
(Class 1,Div 2,Groups A, B, C, D) |
Cenelec EN50021 Zone 2 |
|
Marine/offshore locations |
Det Norske Veritas (DNV) No. 2.4 (Class A and B) |
|
|
|
|
SixTRAK I/O modules (optional) |
|
|
RemoteTRAK I/O modules (optional) |
|
|
EtherTRAK I/O modules (optional) |
Specifications are subject to change. Consult the factory for the latest information.