Product Catalog |
|
q |
|
|
|
|
|
Low Power RemoteLog Performance Specifications
|
On-board I/O |
6 AI, 4 DI and one DO |
|
Maximum I/O, including expansion |
22 analog and/or 20 discrete; add one RemoteTRAK or EtherTRAK module, any model |
|
|
|
|
Analog Inputs |
6 (4-20 mA) – Use Expansion port for other ranges |
|
Input resolution |
0.1% (10 bits) |
|
Input protection |
Self-resetting fuses |
|
|
|
|
Discrete Inputs |
4 (10–30 VDC or switch closure) |
|
Input Current |
8 mA @ 24 VDC |
|
Counting Range |
16 or 32 bits (to over 2 billion counts) |
|
Max count rate |
50 KHz (channel 1 only) 200 Hz (any channel) |
|
|
|
|
Discrete Output |
1 (closure to ground) |
|
Maximum load |
0.25 Amps at 30 VDC |
|
Output functions |
Report alarms or user-controlled output |
|
|
|
|
RS232 Serial Port |
For connection to an external modem |
|
Connections |
(Standard RJ45) TD, RD, CTS, RTS, CD, DTR, RI, GND |
|
Supported Protocols |
Modbus ASCII and RTU, SIXNET Universal |
|
Baud Rate |
All standard rates up to 57,600 baud |
|
|
|
|
Extra Serial Ports (All Models) |
For connection to a local computer and for I/O expansion |
|
System Port Connector |
RS232 DB9 female (standard PC connector) |
|
RS485 Expansion Terminals |
RS485 For one RemoteTRAK module only |
|
|
|
|
Internal Flash Memory |
1 Megabyte (consult factory for more) |
|
Datalogging storage |
40,000 records (all I/O) |
|
Time of day clock |
Run for 30 days without external power |
|
Firmware upgrades |
Reloadable to support future features |
|
|
|
|
General Characteristics |
DIN rail or flat panel mount |
|
Input power |
10-30 VDC |
|
Input current |
8 mA @24 VDC (0.2W) in power saving mode |
|
Operating temperature |
-30° C to 70° C (-40° C to 85° C storage) |
|
Humidity |
5% to 95% RH (non-condensing) |
|
Flammability |
UL 94V-0 materials |
|
Electrical Safety |
UL 508, CSA C22.2/14; EN61010-1 (IEC1010), IEC 950: 1991, AS/NZS3260-1993; |
|
EMI emissions |
FCC part 15, ICES-003, Class A; EN55022; AS/NZS3548-1995; |
|
EMC immunity |
EN50082-1 (IEC801-2, 3, 4) |
|
Surge withstand |
IEEE-472 (ANSI C37.90) |
|
Vibration |
IEC68-2-6 |
|
Hazardous locations |
UL 1604, CSA C22.2/213-M1987, (Class 1, Div 2, Groups A, B, C, D), |
|
Cenelec |
EN50021 (EEx nA II T4) Zone 2 |
|
|
|
|
Electrical safety |
UL 508, CSA C22.2/14; EN61010-1 (IEC1010), CE |
|
EMI emissions |
FCC part 15, ICES-003, Class A; EN55022, CE |
|
EMC immunity |
EN50082-1 (IEC801-2, 3, 4) CE |
|
Surge withstand |
IEEE-472 (ANSI C37.90) |
|
Vibration |
IEC68-2-6 |
|
Hazardous locations |
UL 1604, CSA C22.2/213-M1987, (Class I, Div 2, Groups A, B, C, D), EN50021 (zone 2) |
|
Marine/offshore locations |
Det Norske Veritas (DNV) No. 2.4 (Class A and B) |
Specifications are subject to change. Consult the factory for the latest information.