RS485 Remote I/O |
|
q |
|
|
|
|
|
RM-232-485-4 Performance Specifications
|
Maximum baud rate |
57,600 baud |
|
Protocols supported |
Modbus ASCII / RTU and SIXNET |
|
Wiring configuration |
RS485 two-wire isolated partyline |
|
Isolation (RS485 to RS232 and power) |
1200 Volts RMS 1 minute (see note 2) |
|
RS485 RemoteTRAK ports |
4 ports |
|
Number of RemoteTRAK modules |
32 modules per port, 128 modules total |
|
Maximum RS485 cable distance |
3Km (See note 1 and System Specs) |
|
|
|
|
Serial communication information |
See System Specs |
|
RS485 isolation |
1200 Volts RMS 1 minute |
|
Required supply voltage |
10-30 VDC (0.5 watt typical) |
|
Operating temperature range |
-30 to 70° C |
|
Storage temperature range |
-40 to 85° C |
|
Humidity (non-condensing) |
5 to 95% |
|
Flammability (module plastic) |
UL 94V-0 materials |
|
Electrical safety |
UL 508, CSA C22.2/14; EN61010-1 (IEC1010), CE |
|
EMI emissions |
FCC part 15, ICES-003, Class A; EN55022, CE |
|
EMC immunity |
EN50082-1 (IEC801-2, 3, 4) CE |
|
Surge withstand |
IEEE-472 (ANSI C37.90) |
|
Vibration |
IEC68-2-6 |
|
Hazardous locations |
UL 1604, CSA C22.2/213-M1987, (Class I, Div 2, Groups A, B, C, D), EN50021 (zone 2) |
|
Marine/offshore locations |
Det Norske Veritas (DNV) No. 2.4 (Class A and B) |
Notes:
RS485 distance is limited by baud rate and cable quality. See System Specs.
RS485 ports are group isolated from incoming power and the RS232 port.
Specifications are subject to change. Consult the factory for the latest information.