RS485 Remote I/O |
|
q |
|
|
|
|
|
RM-8DO2 Performance Specifications
|
Number of channels |
8 |
|
Output range |
10-30 VDC |
|
Max. output current per channel |
3 Amps (derate linearly to 2A from 50 to 70° C) |
|
Max. output current (entire module) |
10 Amps |
|
Max. OFF state leakage current |
0.05 mA |
|
Min. load current per channel |
0.1 mA |
|
Inrush current (100 mS surge) |
10 Amps |
|
Maximum inductive load |
0.2H (3 Amp load at 24 VDC) |
|
Typical ON resistance |
0.1 Ohms |
|
Typical ON voltage drop (@1 Amp) |
0.1 VDC |
|
Short circuit protection |
At full rated load |
|
Thermal shutdown protection |
150° C |
|
|
|
|
Serial communication information |
See System Specs |
|
RS485 isolation |
1200 Volts RMS 1 minute |
|
Required supply voltage |
10-30 VDC (0.5 watt typical) |
|
Operating temperature range |
-30 to 70° C |
|
Storage temperature range |
-40 to 85° C |
|
Humidity (non-condensing) |
5 to 95% |
|
Flammability (module plastic) |
UL 94V-0 materials |
|
Electrical safety |
UL 508, CSA C22.2/14; EN61010-1 (IEC1010), CE |
|
EMI emissions |
FCC part 15, ICES-003, Class A; EN55022, CE |
|
EMC immunity |
EN50082-1 (IEC801-2, 3, 4) CE |
|
Surge withstand |
IEEE-472 (ANSI C37.90) |
|
Vibration |
IEC68-2-6 |
|
Hazardous locations |
UL 1604, CSA C22.2/213-M1987, (Class I, Div 2, Groups A, B, C, D), EN50021 (zone 2) |
|
Marine/offshore locations |
Det Norske Veritas (DNV) No. 2.4 (Class A and B) |