RS485 Remote I/O |
|
q |
|
|
|
|
|
RM-PS-024-01F Performance Specifications
|
Output voltage |
+24 VDC |
|
Output power @ 50°C |
24 Watts, 1 Amp |
|
Output power @ 70°C |
18 Watts, 0.75 Amp |
|
Rated for use with |
Any combination of SIXNET and other devices totaling up to 8 watts (nominal). This rating allows sufficient overhead for startup surge. |
|
Line regulation |
0.05 % |
|
Load regulation (0 to full load) |
2 % |
|
Minimum input line voltage |
85 VAC or 120 VDC |
|
Maximum input line voltage |
264 VAC or 370 VDC |
|
Input line frequency |
47 - 63 Hz |
|
Overload protection |
>105% (pulse mode) |
|
Integral EMI filter |
Yes |
|
Safety standards |
UL1950, EN60950, CE |
|
EMC Standards |
CISPR22, EN55022 Class B, CE |
|
Operating temperature range |
-30 to 70° C |
|
Storage temperature range |
-40 to 85° C |
|
Humidity (non-condensing) |
5 to 95 % |
|
Flammability (module plastic) |
UL 94V-0 materials |
|
Electrical safety |
UL 508, CSA C22.2/14; EN61010-1 (IEC1010), CE |
|
EMI emissions |
FCC part 15, ICES-003, Class A; EN55022, CE |
|
EMC immunity |
EN50082-1 (IEC801-2, 3, 4) CE |
|
Surge withstand |
IEEE-472 (ANSI C37.90) |
|
Vibration |
IEC68-2-6 |
|
Hazardous locations |
UL 1604, CSA C22.2/213-M1987, (Class I, Div 2, Groups A, B, C, D), EN50021 (zone 2) |
|
Marine/offshore locations |
Det Norske Veritas (DNV) No. 2.4 (Class A and B) |
Specifications are subject to change. Consult the factory for the latest information.