Product Catalog |
|
|
|
q |
|
|
|
RemoteTRAK Communication Specifications
|
Protocols supported |
Modbus ASCII/RTU and SIXNET Universal |
|
Wiring Configuration |
|
|
RS485 isolation |
1200 Volts RMS 1 minute (module to module) |
|
Supported baud rates |
2400, 9600, 19200, 38400, 57600 baud |
|
Factory configuration |
9600 baud, no parity, 8 data bits, SIXNET protocol |
|
Cable recommendation |
Shielded, twisted pair with drain wire desirable. Data rated cable is recommended for greater distances. |
|
RS485 Limitations: |
|
|
Cable length up to 1 km |
24 AWG and 57600 baud |
|
Cable length up to 2 km |
20 AWG and 38400 baud |
|
Cable length up to 3.5 km |
18 AWG and 19200 baud |
|
# Modules on RS485 network |
32 maximum |
|
# Addressable modules |
128 with a RM-232-485-4U |
RemoteTRAK Environmental Specifications
|
Operating temperature range |
-30 to 70° C |
|
Storage temperature range |
-40 to 85° C |
|
Humidity (non-condensing) |
5 to 95% (consult factory for conformal coating options) |
|
Flammability (module plastic) |
UL 94V-0 materials |
|
Electrical safety |
UL 508, CSA C22.2/14; EN61010-1 (IEC1010), CE |
|
EMI emissions |
FCC part 15, ICES-003, Class A; EN55022, CE |
|
EMC immunity |
EN50082-1 (IEC801-2, 3, 4), CE |
|
Surge withstand |
IEEE-472 (ANSI C37.90) |
|
Hazardous locations |
UL 1604, CSA C22.2/213-M1987, (Class I, Div 2, Groups A, B, C, D), EN50021 (zone 2) |
|
Marine/offshore locations |
Det Norske Veritas (DNV) No. 2.4 (Class A and B) |
Specifications are subject to change. Consult the factory for the latest information.