The instrumentation analog input module is ideal for one or more of the following applications:
|
¢ |
Thermocouple temperature measurements |
|
¢ |
Volt or millivolt readings |
|
¢ |
Floating (off ground) 4-20 mA readings |
|
¢ |
Any combination of the above ranges |
|
¢ |
For accuracy better than 0.05% |
|
¢ |
For true differential performance (superior ground loop rejection) |
Current Loop Inputs (4-20 mA channels)
A 100-ohm precision current shunt is present in the base of all analog input modules that read 4-20mA instrumentation loop signals. If a module is unplugged, current continues to flow in the loop.
The instrumentation module supports multiple input ranges and must only have this shunt across the input for each 4-10 mA input. Access the shunt selection jumper for each channel by opening the base access door (with the module removed).
Note:
You must set the current shunt jumper inside the base (open the door) for
4-20 mA channels. Current shunts act as fuses if overloads occur (typically
from shorted transmitters). These shunts are field replaceable. A spare
shunt is stored inside the base access door.
Instrument loops can be protected from over current by using a ST-CL-20M-16H module.