SixTRAK Local I/O |
|
q |
|
|
|
|
|
ST-AO-20M-04F Performance Specifications
|
Number of channels |
4 |
|
Output range |
4-20 mA |
|
D/A resolution |
13 bits |
|
Output resolution |
2 uA |
|
Guaranteed accuracy |
+/- .05 % (@ 20° C) |
|
Output linearity |
+/- .02 % (@ 20° C) |
|
Output span adjustment |
+/- 25 % |
|
Output offset adjustment |
+/- 25 % |
|
Span temperature coefficient |
+/- 50 ppm/ degree C |
|
Offset temperature coefficient |
+/- 50 ppm/ degree C |
|
Maximum output settling time |
5 mS (to 0.05%) |
|
User loop voltage |
10-30 volts |
|
Load resistance |
0-750 ohms (at +24 volt supply) |
|
|
|
|
Maximum ST-Bus power |
500 mW |
|
Isolation (from ST-Bus) |
1200 VDC |
|
Operating temperature range |
-30 to 70 degrees C |
|
Storage temperature range |
-40 to 85 degrees C |
|
Humidity (non-condensing) |
5 to 95 % |
|
Flammability (module plastic) |
UL 94V-0 materials |
|
Electrical safety |
UL 508, CSA C22.2/14; EN61010-1 (IEC1010), CE |
|
EMI emissions |
FCC part 15, ICES-003, Class A; EN55022, CE |
|
EMC immunity |
EN50082-1 (IEC801-2, 3, 4) CE |
|
Surge withstand |
IEEE-472 (ANSI C37.90) |
|
Vibration |
IEC68-2-6 |
|
Hazardous locations |
UL 1604, CSA C22.2/213-M1987, (Class I, Div 2, Groups A, B, C, D), EN50021 (zone 2) |
|
Marine/offshore locations |
Det Norske Veritas (DNV) No. 2.4 (Class A and B) |