SixTRAK Local I/O |
|
q |
|
|
|
|
|
ST-DI-CNT-08U Performance Specifications
|
Number of counters |
8 |
|
Count mode performance: |
|
|
Guaranteed count rate |
50 KHz |
|
Count resolution |
16 bits |
|
Rate (frequency) mode performance: |
|
|
Maximum input rate |
50,000 per sec |
|
Shortest measurement period |
100 mS |
|
Longest measurement period |
1 min |
|
Position mode performance: |
|
|
Maximum position axes |
|
|
(two channels per axis) |
4 |
|
Maximum pulses per second |
25,000 |
|
Maximum quadrature states |
100,000 per second |
|
Position resolution |
32 bits |
|
Input performance: |
|
|
Guaranteed count input voltage |
4 volts |
|
Maximum count input voltage |
30 volts |
|
Guaranteed off input voltage |
1.5 volts |
|
Nominal count input current |
8 mA |
|
|
|
|
Maximum ST-Bus power |
600 mW |
|
Isolation (input to ST-Bus) |
1200 V |
|
Operating temperature range |
-30 to 70 degrees C |
|
Storage temperature range |
-40 to 85 degrees C |
|
Humidity (non-condensing) |
5 to 95 % |
|
Flammability (module plastic) |
UL 94V-0 materials |
|
Electrical safety |
UL 508, CSA C22.2/14; EN61010-1 (IEC1010), CE |
|
EMI emissions |
FCC part 15, ICES-003, Class A; EN55022, CE |
|
EMC immunity |
EN50082-1 (IEC801-2, 3, 4) CE |
|
Surge withstand |
IEEE-472 (ANSI C37.90) |
|
Vibration |
IEC68-2-6 |
|
Hazardous locations |
UL 1604, CSA C22.2/213-M1987, (Class I, Div 2, Groups A, B, C, D), EN50021 (zone 2) |
|
Marine/offshore locations |
Det Norske Veritas (DNV) No. 2.4 (Class A and B) |
Note: A pair of counter channels can be combined to make a 32 bit up/down counter or accumulator.