image\st-logo2_wmf.gif

SixTRAK Local I/O
8 Channel
Discrete Outputs

q

 

 

 

 

 

image\btn_Specifications.gif

image\btn_Wiring.gif

image\btn_Usage.gif

image\btn_Ordering.gif

image\btn_Large_Image32.gif

image\btn_Data_Sheet32.gif

 

ST-DO-AC1-08U Performance Specifications

Number of channels

8

Minimum output voltage

16 VAC

Maximum output voltage

140 VAC

Minimum load current

10 mA (per output)

Maximum load current

 

at 50 degrees C 

2 Amps (per output)

at 70 degrees C 

1.5 Amps (per output)

Maximum load current

 

Field Base 

8 Amps (per module)

Universal Base 

8 Amps (per module)

Max OFF state leakage current

2 mA

Inrush current (100 mS surge)

6 Amps

Typical ON voltage drop

1.0 VAC (@ 1 Amp)

Channel to channel isolation

500 V with U base

 

 

Maximum ST-Bus power

600 mW

Isolation (input to ST-Bus)

1200 V

Operating temperature range

-30 to 70 degrees C

Storage temperature range

-40 to 85 degrees C

Humidity (non-condensing)

5 to 95 %

Flammability (module plastic)

UL 94V-0 materials

Electrical safety

UL 508, CSA C22.2/14; EN61010-1 (IEC1010), CE

EMI emissions

FCC part 15, ICES-003, Class A; EN55022, CE

EMC immunity

EN50082-1 (IEC801-2, 3, 4) CE

Surge withstand

IEEE-472 (ANSI C37.90)

Vibration

IEC68-2-6

Hazardous locations

UL 1604, CSA C22.2/213-M1987, (Class I, Div 2, Groups A, B, C, D), EN50021 (zone 2)

Marine/offshore locations

Det Norske Veritas (DNV) No. 2.4 (Class A and B)

 

Note: The first output may be configured as a system performance watchdog. ON=OK.

 