SixTRAK Local I/O |
|
q |
|
|
|
|
|
ST-DO-AC2-08U Performance Specifications
|
Number of channels |
8 |
|
Minimum output voltage |
140 VAC |
|
Maximum output voltage |
265 VAC |
|
Minimum load current |
10 mA (per output) |
|
Maximum load current |
|
|
at 50 degrees C |
2 Amps (per output) |
|
at 70 degrees C |
1.5 Amps (per output) |
|
Maximum load current |
|
|
Field Base |
8 Amps (per module) |
|
Universal Base |
8 Amps (per module) |
|
Max OFF state leakage current |
2 mA |
|
Inrush current (100 mS surge) |
6 Amps |
|
Typical ON voltage drop |
1.0 VAC (@ 1 Amp) |
|
Channel to channel isolation |
500 V with U base |
|
|
|
|
Maximum ST-Bus power |
600 mW |
|
Isolation (input to ST-Bus) |
1200 V |
|
Operating temperature range |
-30 to 70 degrees C |
|
Storage temperature range |
-40 to 85 degrees C |
|
Humidity (non-condensing) |
5 to 95 % |
|
Flammability (module plastic) |
UL 94V-0 materials |
|
Electrical safety |
UL 508, CSA C22.2/14; EN61010-1 (IEC1010), CE |
|
EMI emissions |
FCC part 15, ICES-003, Class A; EN55022, CE |
|
EMC immunity |
EN50082-1 (IEC801-2, 3, 4) CE |
|
Surge withstand |
IEEE-472 (ANSI C37.90) |
|
Vibration |
IEC68-2-6 |
|
Hazardous locations |
UL 1604, CSA C22.2/213-M1987, (Class I, Div 2, Groups A, B, C, D), EN50021 (zone 2) |
|
Marine/offshore locations |
Det Norske Veritas (DNV) No. 2.4 (Class A and B) |
Note: The first output may be configured as a system performance watchdog. ON=OK.