image\st-logo2_wmf.gif

SixTRAK Local I/O
8 Channel Discrete Output
s

q

 

 

 

 

 

image\btn_Specifications.gif

image\btn_Wiring.gif

image\btn_Usage.gif

image\btn_Ordering.gif

image\btn_Large_Image32.gif

image\btn_Data_Sheet32.gif

 

ST-DO-DC3-08U Performance Specifications

Number of channels

8

Minimum output voltage

60 VDC

Maximum output voltage

150 VDC

Minimum load current

0.1 mA (per output)

Maximum load current

1 Amp (per output) up to 70° C

Maximum load current

 

Field Base 

8 Amps (per module)

Universal Base 

8 Amps (per module)

Note: Load current limited by FET resistance.

 

Max OFF state leakage current

10 uA

Inrush current (100 mS surge)

10 Amps

Typical ON resistance

0.25 ohms

Typical ON voltage drop

0.3 VDC (@ 1 Amp)

Channel to channel isolation

500 V with U base

 

 

Maximum ST-Bus power

600 mW

Isolation (input to ST-Bus)

1200 V

Operating temperature range

-30 to 70 degrees C

Storage temperature range

-40 to 85 degrees C

Humidity (non-condensing)

5 to 95 %

Flammability (module plastic)

UL 94V-0 materials

Electrical safety

UL 508, CSA C22.2/14; EN61010-1 (IEC1010), CE

EMI emissions

FCC part 15, ICES-003, Class A; EN55022, CE

EMC immunity

EN50082-1 (IEC801-2, 3, 4) CE

Surge withstand

IEEE-472 (ANSI C37.90)

Vibration

IEC68-2-6

Hazardous locations

UL 1604, CSA C22.2/213-M1987, (Class I, Div 2, Groups A, B, C, D), EN50021 (zone 2)

Marine/offshore locations

Det Norske Veritas (DNV) No. 2.4 (Class A and B)

 

Note: The first output may be combined as a system performance watchdog. ON=OK.

 

Specifications are subject to change. Consult the factory for the latest information.