image\st-logo2_wmf.gif

SixTRAK Local I/O
24 VDC Power Supply

q

 

 

 

 

 

image\btn_Specifications.gif

image\btn_Wiring.gif

image\btn_Usage.gif

image\btn_Ordering.gif

image\btn_Large_Image32.gif

image\btn_Data_Sheet32.gif

 

ST-PS-024-02N Performance Specifications

Output voltage

+24 VDC

Line regulation

0.05 %

Load regulation (0 to full load)

2 %

Temperature regulation

0.04% per degree C

Rated output power:

 

(at 50º C and any line voltage) 

48 Watts, 2 Amps

(at 70º C and 90-135 VAC input) 

36 Watts, 1.5 Amps

(at 70º C and 135-260 VAC input) 

24 Watts, 1 Amp

Minimum input line voltage

90 VAC

Maximum input line voltage

260 VAC

Input line frequency

47-63 Hz 

Guaranteed no drop out

1 cycle

Overvoltage protection

26.5 to 30 VDC

Overcurrent protection

Current limiting

 

 

Operating temperature range

-30 to 70 degrees C

Storage temperature range

-40 to 85 degrees C

Humidity (non-condensing)

5 to 95 %

Flammability (module plastic)

UL 94V-0 materials

Electrical safety

UL 508, CSA C22.2/14; EN61010-1 (IEC1010), CE

EMI emissions

FCC part 15, ICES-003, Class A; EN55022, CE

EMC immunity

EN50082-1 (IEC801-2, 3, 4) CE

Surge withstand

IEEE-472 (ANSI C37.90)

Vibration

IEC68-2-6

Hazardous locations

UL 1604, CSA C22.2/213-M1987, (Class I, Div 2, Groups A, B, C, D), EN50021 (zone 2)

Marine/offshore locations

Det Norske Veritas (DNV) No. 2.4 (Class A and B)

 

Specifications are subject to change. Consult the factory for the latest information.