SixTRAK Local I/O |
|
|
|
|
|
|
ST-Bus Wiring Guidelines
|
Max. modules controlled by one station |
20 |
|
Required cable type |
Any with 2 individually shielded pairs, 22 AWG min |
|
Recommended cables |
Alpha 2466C, Belden 8723, Carol C1352 |
|
Max cabling off each station |
50 ft (16 M) |

Connect up to 20 I/O modules directly to a station with a maximum total cabling of 50 ft.

Use an I/O Concentrator (ET-GT-ST-2 or –3) if you need more than 20 I/O modules.

ST-Bus connections may be wired in star configurations without restrictions.

Route ST-Bus wiring away from power wiring and sources of electrical interference.

Use an I/O Concentrator (ET-GT-ST-2 or –3) or other Sixnet station to interface SixTRAK I/O in additional cabinets. Make Ethernet or serial connections between stations as needed.

Use the supplied ST-Bus jumpers between directly adjacent SixTRAK components. Otherwise, use the recommended cable.