VT-PB8 Performance Specifications

VT-PB8:

 

Number of channels

Module type used

single point discrete I/O modules 

Mix of inputs and outputs

Any 

 

 

Discrete input modules

 

IDC-01

10 - 32 VDC

IDC-11

3 - 12 VDC

IDC-21

20 - 120 VDC

IAC-01

90 - 140 VAC 

IAC-11

180 - 280 VAC 

IAC-21

10 - 32 VAC 

 

 

Discrete output modules

 

ODC-01

3 - 60 VDC (10 mA - 3A)  

OAC-01

20 - 140 VAC (50 mA - 3A) 

OAC-11

140 - 280 VAC (50 mA - 3A) 

 

 

Isolation from circuitry

1200 V 

Isolation module to module

500 V 

Operating temperature range

-30 to 70 degrees C 

Storage temperature range

-40 to 85 degrees C 

Humidity (non-condensing)

5 to 95 % 

Flammability (module plastic)

UL 94V-0 materials

Electrical safety

UL 508, CSA C22.2/14; EN61010-1 (IEC1010), CE

EMI emissions

FCC part 15, ICES-003, Class A; EN55022, CE

EMC immunity

EN50082-1 (IEC801-2, 3, 4) CE

Surge withstand

IEEE-472 (ANSI C37.90)

Vibration

IEC68-2-6

Hazardous locations

UL 1604, CSA C22.2/213-M1987, (Class I, Div 2, Groups A, B, C, D), EN50021 (zone 2)

Marine/offshore locations

Det Norske Veritas (DNV) No. 2.4 (Class A and B)

 